ASAP Semiconductor

Request an Instant Quote for Part SB1612-5

If you are in need of parts such as SB1612-5 - Pole Quantity: 1 Maximum Continuous Load Current Rating per Pole: 30.0 amperes ac single location Operating Voltage Type and Rating per Pole in Volts: 125.0 ac single location from Eaton Corporation, look no further than ASAP Inventory. As a wholly-owned subsidiary of ASAP Semiconductor, we have access to an inventory of more than two billion new and obsolete parts and components such as SB1612-5 and many more. ASAP Inventory is an AS9120B, ISO 9001:2015, and FAA AC 00-56B accredited business, and the only independent distributor with a strict No China Sourcing Pledge, helping ensure each part purchased is fully traceable or sourced directly from the manufacturer. Anything not currently in inventory can be sourced and delivered with short lead times and competitive pricing through our international supply chain network spanning North America and Europe.Our website offers parametric search capabilities that allow customers to search for parts through multiple filters, including National Stock Number identification. A National Stock Number is assigned to items repeatedly procured, stocked, issued, and used throughout the federal supply system. ASAP Inventory maintains a broad selection of NSN parts such as SB1612-5 from manufacturers like Eaton Corporation. To begin the purchasing process immediately, submit an RFQ today.

Specifications

Part NumberSB1612-5
DescriptionPole Quantity: 1 Maximum Continuous Load Current Rating per Pole: 30.0 amperes ac single location Operating Voltage Type and Rating per Pole in Volts: 125.0 ac single location
ManufacturerEaton Corporation
NSN5925-00-299-7809(5925002997809)
Item NamePole Quantity: 1 Maximum Continuous Load Current Rating per Pole: 30.0 amperes ac single location Operating Voltage Type and Rating per Pole in Volts: 125.0 ac single location
CAGE Code0AXU3
NIIN00-299-7809(002997809)
FSC Code5925 Circuit Breakers
FSG Code59 Electrical and Electronic Equipment Components
NCB Code00
CountryUSA

Description

Pole Quantity: 1 Maximum Continuous Load Current Rating per Pole: 30.0 amperes ac single location Operating Voltage Type and Rating per Pole in Volts: 125.0 ac single location

Request a Quote

22% complete
Part Information
Contact Information
  • I consent to receive email communications from ASAP Semiconductor and can unsubscribe at any time.
  • ASAP Semiconductor is a wholly independent aftermarket parts distributor.
  • This website is intended for quotations based on part numbers only. Please DO NOT submit drawings, technical data, or other specifications through this portal.

If You Have Multiple Parts Requirement, You Can Upload Your Parts List or BOM Here!

Characteristics Data of NSN 5925-00-299-7809, 5925002997809

MRCCriteriaCharacteristic
AAQLBODY STYLESINGLE POLE TYPE
ADAQBODY LENGTH3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM
ADATBODY WIDTH0.980 INCHES MINIMUM AND 1.000 INCHES MAXIMUM
ADTVCASE MATERIALPLASTIC
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHT0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCE2.611 INCHES NOMINAL
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC SINGLE LOCATION
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC SINGLE LOCATION
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 AC SINGLE LOCATION
CPRHCIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
CPRJTRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
CPRLTRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
CQJXNOMINAL THREAD SIZE0.138 INCHES
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5.500 MINIMUM AT 200 PCT SINGLE LOCATION AND 19.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
FREQFREQUENCY IN HERTZ60.0 SINGLE LOCATION
THSDTHREAD SERIES DESIGNATORUNC
TTQYTERMINAL TYPE AND QUANTITY2 THREADED STUD